Type:  Remote Terminal Unit
Description:  Remote Terminal Unit designed for electric power utility and telecommunications industries
Connectivity:  Modbus
Features:  Output relays can handle 0.6 Amps at 125Vac or 2 Amps at 30Vdc and can be used in Select-Before-Operate or Direct Operate modes; Eight status inputs can be independently configured for Active-HI and/or Active-LO operation; Two RS-232 ports and one Ethernet port; Can be configured for DNP 3.0, Modbus, PG&E, Landis & Gyr 8979, or CDC Type-1 protocols; Comes with a free copy of VisiCal software suite that allows it to be configured, calibrated, scanned, monitored or programmed with drag-and-drop and pushbutton simplicity
Specifications:  Control Points: 4 Relays; Control Sequence: Direct or SBO; Relay Contacts: Form C, 0.6 Amps at 125Vac or 2 Amps at 30Vdc; Status Inputs: 8; Status Input Voltage: 12Vdc to 35Vdc; Input Current: .1ma (typical); Isolation: Optical; Overvoltage: phase-to-phase 460V for 10 minutes; Phase-to-Ground 2000V; Input Voltage: 12Vdc (4 watts); Communication Link: 2 RS-232 Ports & 1 Ethernet Port; SWC Certification: ANSI/IEEE C37.90.1 SWC Certified; Dimensions: 7.0" x 7.4" x 1.6"; Also Available as a Bare Card or in a NEMA-4 Box;